Water Blocked P7 or P7/P14 BFOU 6/10kV
Applications
-
These cables are partially water blocked, fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.
Standards
IEC 60092-354 | IEC 60092-351 |
IEC 60092-359 | IEC 60332-1 |
IEC 60331-21 | IEC 60332-3-22 |
IEC 60754-1,2 | IEC 61034-1,2 |
NEK 606:2004 | VG 95218 part 29 |
Construction
-
l Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l Conductor Screen: Semi conducting material.
l Insulation: Mica tape + Halogen free EPR.
l Insulation Screen: Semi conducting material and tinned copper wire braid.
l Filler: Water blocking fillers, if required.
l Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the
braiding, if required.
l Water Blocking Elements: Water blocking tape and strings for providing longitudinal
water tightness.
l Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P7), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P7/P14), coloured red.
l Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Electrical Characteristics
-
Nominal Cross Section Area mm² 25 35 50 70 95 120 150 Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1 Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126 Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339 389 Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237 272 Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170 21460 Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
-
Nominal Cross Section Area mm² 185 240 300 400 500 630 Nominal Conductor Diameter mm 17.0 19.6 21.9 24.5 27.5 32.3 Maximum DC Resistant@20℃ Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286 Continuous Current Rating@45℃1 Core A 444 522 601 690 780 890 Continuous Current Rating@45℃3 Core A 311 365 421 483 546 623 Short Circuit Current 1s A 26470 34340 42930 57230 71540 90140 Operating Voltage KV 6/10 6/10 6/10 8.7/15 8.7/15 8.7/15
Ambient Temperature Correction Factors
Ambient Temperature Correction Factors | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
Rating Factor | 1.1 | 1.05 | 1.0 | 0.94 | 0.88 | 0.82 | 0.74 | 0.67 | 0.58 | 0.47 |
Mechanical and Thermal Properties
- Bending Radius :15×OD (during installation); 9×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight
Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm | Nominal Bedding Thickness mm |
Nominal Inner Sheath Thickness mm |
Nominal Outer Sheath Thickness mm |
Nominal Overall Diameter mm |
|
Nominal Weight kg/km |
||||||
1×16 | 3.4 | 1.5 | 1.2 | 1 | 27.6±2 | 1040 |
1×25 | 3.4 | 1.6 | 1.2 | 1.2 | 29.5±2 | 1208 |
1×35 | 3.4 | 1.7 | 1.2 | 1.2 | 30.9±2 | 1386 |
1×50 | 3.4 | 1.7 | 1.3 | 1.2 | 32.3±2 | 1575 |
1×70 | 3.4 | 1.8 | 1.3 | 1.2 | 34.3±2 | 1901 |
1×95 | 3.4 | 1.8 | 1.4 | 1.4 | 36.8±2 | 2268 |
1×120 | 3.4 | 1.9 | 1.4 | 1.4 | 38.9±2 | 2741 |
1×150 | 3.4 | 2 | 1.5 | 1.4 | 40.9±2 | 3140 |
1×185 | 3.4 | 2 | 1.5 | 1.4 | 42.7±2 | 3612 |
1×240 | 3.4 | 2.2 | 1.6 | 1.6 | 46.3±2 | 4389 |
1×300 | 3.4 | 2.3 | 1.7 | 1.6 | 49.1±2 | 5177 |
1×400 | 3.4 | 2.4 | 1.7 | 1.6 | 52.2±2 | 6195 |
1×500 | 3.4 | 2.5 | 1.8 | 1.6 | 55.7±2 | 7424 |
1×630 | 3.4 | 2.7 | 1.9 | 1.6 | 60.2±2 | 9125 |
3×16 | 3.4 | 2.4 | 1.8 | 1 | 52.2±2 | 3969 |
3×25 | 3.4 | 2.5 | 1.8 | 1.2 | 55.6±2 | 4599 |
3×35 | 3.4 | 2.6 | 1.9 | 1.2 | 58.8±2 | 5292 |
3×50 | 3.4 | 2.7 | 2 | 1.2 | 61.7±2 | 6027 |
3×70 | 3.4 | 2.9 | 2.1 | 1.2 | 66.1±2 | 7245 |
3×95 | 3.4 | 3.1 | 2.2 | 1.4 | 71.2±2 | 8684 |
3×120 | 3.4 | 3.2 | 2.3 | 1.4 | 74.9±2 | 9944 |
3×150 | 3.4 | 3.3 | 2.4 | 1.4 | 78.8±2 | 11340 |
3×185 | 3.4 | 3.5 | 2.5 | 1.4 | 83.6±2 | 12989 |
3×240 | 3.4 | 3.7 | 2.7 | 1.6 | 91.4±2 | 15792 |
3×300 | 3.4 | 3.9 | 2.9 | 1.6 | 97.2±2 | 18323 |